Skip to main content Skip to search Skip to main navigation

EAST EA902PSRT Online UPS 2000VA (1800W), 19" rack 2U, LCD, RS232 (EA902SPRT_EPO)

Product "EAST EA902PSRT Online UPS 2000VA (1800W), 19" rack 2U, LCD, RS232 (EA902SPRT_EPO)"

EAST EA902PSRT is a 2000 VA / 1800 W double-conversion (online) UPS for a 19-inch rack. Unlike a cheaper line-interactive unit it never switches the load between mains and battery — the output is rebuilt continuously, so the equipment always sees a clean sine wave and the transfer time is 0 ms.

Key Advantages and Features:

  • True double conversion: The output is rebuilt continuously, so mains sags, frequency drift and noise never reach the load. Transfer from mains to battery takes 0 ms.
  • Wide input range: Works from 110–300 V and 40–70 Hz — the battery is only used when the mains is genuinely gone, which preserves battery life.
  • Easy on the mains: Active power factor correction keeps the input power factor up to 0.99 and distortion below 6 %.
  • ECO mode: Up to 96 % efficiency in ECO mode — less heat and a smaller electricity bill.
  • Cold start: Starts from battery alone with no mains present — useful when the power is already out before the equipment is switched on.
  • LCD menu and RS232: Output voltage, EOD, auto-start and bypass mode are set from the LCD. RS232 is standard; USB, RS485, dry contacts and an SNMP card are optional.
  • Hot-swap batteries and ABM: Batteries can be replaced without dropping the load; ABM charging restores 90 % of capacity in three hours.
  • Rack or tower: The 2U housing fits a 19-inch rack, and with the included feet it can stand upright instead.

Technical Specifications:

ParameterSpecification
TypeOnline double conversion (VFI), transformerless
Capacity2000 VA / 1800 W (output power factor 0.9)
Input voltage208 / 220 / 230 / 240 V AC; range 110–300 V
Input frequency40–70 Hz (auto-sensing)
Input power factor≥ 0.99; THDi ≤ 6 %
Output voltage208 / 220 / 230 / 240 V AC (settable on the LCD), ± 1 %
Output waveformsine wave; THDv ≤ 2 % (linear load), ≤ 5 % (non-linear)
Overload105–125 % for 1 min, 125–150 % for 30 s, over 150 % for 300 ms
Transfer timemains to battery 0 ms; inverter to bypass 4 ms
CommunicationsRS232 (standard); USB, RS485, dry contacts, SNMP (optional)
DisplayLCD + LED
Protectionsshort circuit, overload, overtemperature, battery discharge, fan failure
Noise level≤ 50 dB at 1 m
Working temperature0–40 °C; humidity 0–95 % (non-condensing)
Protection ratingIP20
StandardsEN 62040-1, EN 62040-2, EN 61000-3-2, EN 61000-3-3, IEC 62040-1/-2
Efficiency≥ 91 % mains mode, ≥ 86 % battery mode, ≥ 96 % ECO mode
Batteriesinternal batteries, 48 V (4 × 9 Ah); charging current 1 A, 90 % of capacity in 3 hours
Dimensions (W × D × H)440 × 430 × 88 mm (2U)
Packaged545 × 560 × 201 mm
Weight15.5 kg (18.6 kg packaged)

Suited to a rack behind a recorder, switch and network gear, and to a workstation or point-of-sale system that cannot tolerate even a momentary dropout. Runtime depends on the load — 1800 W is the peak rating, not a runtime promise; for longer autonomy see the 3 kVA model of the same series with an external battery cabinet.

Properties "EAST EA902PSRT Online UPS 2000VA (1800W), 19" rack 2U, LCD, RS232 (EA902SPRT_EPO)"
Product type: UPS
Datasheets
Tooteleht (PDF)

Oops! Your browser doesn't support PDFs!

Manufacturer "EAST"

0 of 0 reviews

Average rating of 0 out of 5 stars

Leave a review!

Share your experiences with other customers.